Issue overview
In the VRF physics-based model indoor unit coil calculation, the subcooling degree is adjusted only when the demand (or capacity limit imposed by the outdoor unit) is very small. In this example, the initial subcooling degree from user input is 11.5C. No matter how the system capacity (both the condenser and coil) changes, the subcooling degree does not go below 11.5C.
When the control target (the minimum of total IU output and the capacity limit imposed by the condenser through limitTUCapacity function) is in case 4, subcooling degree (SC) is kept at the initial value. There should be some further adjustment (decrease) to increase indoor unit capacity.
Details
Some additional details for this issue (if relevant):
- Platform (MacOS, 13.5)
- Version of EnergyPlus (23.1)
- Unmethours link or helpdesk ticket number
Defect files
idf
US+SF+CZ4A+hp+crawlspace+IECC_2006_VRF_cap4000.idf.txt
US+SF+CZ4A+hp+crawlspace+IECC_2006_VRF_cap7000.idf.txt
US+SF+CZ4A+hp+crawlspace+IECC_2006_VRF_cap10000.idf.txt
US+SF+CZ4A+hp+crawlspace+IECC_2006_VRF_cap15000.idf.txt
epw
USA_NY_New.York-John.F.Kennedy.Intl.AP.744860_TMY3.epw.txt