Chilled water cooling coil has water deltaT with no airflow or air deltaT across coil #7908

@matthew-larson

Description

@matthew-larson

Issue overview

The screenshot below shows the inlet and outlet flow rates and temperatures of the air and water across a chilled water cooling coil. From 24:00 to 5:00, there is no air flow across the coil and no change in air temperature from the inlet and outlet, yet there is chilled water flow through the coil with a temperature increase of 3-4C. Even with water flow through the coil, there shouldn't be an increase in chilled water temperature through the coil if there is no air flow. The Cooling Coil Total Cooling Energy output does report 0 energy consumption during this period.

image

Details

Some additional details for this issue (if relevant):

  • EnergyPlus v9.3

Checklist

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Defect file added (list location of defect file here)
  • Ticket added to Pivotal for defect (development team task)
  • Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)