Notation

Command Line Interface

These examples make heavy use of a command line interface. Due to Python's excellent portability this may be on the operating system of your choice: cmd.exe on Windows or your favorite shell on Linux and macOS.

When a shell asks for user input, it presents a prompt whose appearance may vary: from an angle bracket (>) at cmd.exe to a dollar ($) or percentage sign (%) on Linux or macOS. The examples will use the dollar sign ($) to indicate an input prompt and the example

$ bsmtool version
0.12.0

means enter bsmtool version at your shell prompt and the expected output will be 0.12.0 here.

There are a few advanced examples command line invocations using command pipeline (|). They work on typical shells on Linux and macOS but your results on Windows may vary.

Modbus

Interaction with the Device

Most of the examples will use the BSM Tool to perform the interaction with the BSM-WS36A and the actual Modbus frames sent over the wire. Requests to the meter are indicated by a right arrow --> and responses by a left arrow <--.

For example, reading the common block, which could be seen as the electronic nameplate of the device is done by invoking

$ bsmtool get cb
common:
    Mn: BAUER Electronic
    Md: BSM-WS36A-H01-1311-0000
    Opt: None
    Vr: 1.9:32CA:AFF4
    SN: 21070006
    DA: 42

which results in the following Modbus frames being sent to and from the device:

--> 2a 03 9c44 0042 ada5
<-- 2a 03 84 424155455220456c656374726f6e69630000000000000000000000000000000042534d2d57533336412d4830312d313331312d3030303000000000000000000000000000000000000000000000000000312e393a333243413a414646340000003231303730303036000000000000000000000000000000000000000000000000002a8000 890d

Register Contents

For pointing out the actual data register dumps will be used. Such dumps could be generated with the BSM Tool using protocol addresses:

$ bsmtool dump 40002 68
   40002: 0001 0042 4241 5545 5220 456c 6563 7472  ...BBAUER Electr
   40010: 6f6e 6963 0000 0000 0000 0000 0000 0000  onic............
   40018: 0000 0000 4253 4d2d 5753 3336 412d 4830  ....BSM-WS36A-H0
   40026: 312d 3133 3131 2d30 3030 3000 0000 0000  1-1311-0000.....
   40034: 0000 0000 0000 0000 0000 0000 0000 0000  ................
   40042: 0000 0000 312e 393a 3332 4341 3a41 4646  ....1.9:32CA:AFF
   40050: 3400 0000 3231 3037 3030 3036 0000 0000  4...21070006....
   40058: 0000 0000 0000 0000 0000 0000 0000 0000  ................
   40066: 0000 0000 002a 8000                      .....*..

An output line starts with the decimal protocol address of the first register in this line. It is followed by a hexadecimal representation of the register contents. At the end of the line, the data is interpreted as ASCII characters where possible and dots also represent non-printable characters.

The example above includes two registers of header data starting at protocol address 40002/data address 40003.