Architecture Documentation

System Overview

ya-modbus is a TypeScript monorepo that bridges Modbus devices (RTU/TCP) to MQTT, solving critical challenges in multi-device deployments:

  1. Bus collision prevention - Automatic mutex for RTU serial buses
  2. Adaptive polling - Different rates for dynamic vs static registers
  3. Runtime reconfiguration - Add/modify/remove devices via MQTT
  4. Device discovery - Auto-detect devices and connection parameters
  5. Production monitoring - Comprehensive diagnostics and error publishing

Core Architecture

Package Structure

@ya-modbus/mqtt-bridge     - Bridge orchestration, MQTT publishing, polling
@ya-modbus/cli             - Command-line tools
@ya-modbus/transport       - RTU/TCP transport implementations
@ya-modbus/driver-types    - TypeScript type definitions (types-only)
@ya-modbus/driver-sdk      - Runtime SDK (base classes, helpers, transforms)
@ya-modbus/driver-loader   - Dynamic driver loading
@ya-modbus/device-profiler - Device discovery and register scanning
@ya-modbus/emulator        - Software Modbus emulator for testing
@ya-modbus/driver-*        - Device driver implementations (e.g., driver-ex9em, driver-xymd1)

Core Dependencies

Modbus Protocol: Uses modbus-serial package for Modbus RTU and TCP communication.

  • Supports serial ports (RS-485/RS-232) and TCP connections
  • Handles low-level protocol framing and CRC
  • Provides async/await interface for operations

Why modbus-serial: Mature, well-tested library with active maintenance and broad device compatibility.

Version: ^8.0.25 in @ya-modbus/transport and @ya-modbus/emulator.

Where it is used:

  • Client side: ModbusRTU in @ya-modbus/transport (RTU and TCP) and in the discovery scanner of @ya-modbus/cli
  • Server side: ServerTCP and ServerSerial in @ya-modbus/emulator

Known constraint (emulator): modbus-serial does not await a Promise returned by the multi-register read functions of a server service vector (getMultipleHoldingRegisters, getMultipleInputRegisters), although its types allow it. The emulator uses the callback style for all read functions of its service vector (src/transports/service-vector.ts, shared by the TCP and RTU transports). This is an internal detail and does not change the public API. The workaround is limited to these read functions, so the emulator keeps modbus-serial. See packages/emulator/README.md (Known Limitations).

Layered Architecture

┌─────────────────────────────────────────────────────────┐
│                    MQTT Interface                       │
│  (Configuration, Status, Data Publishing, Discovery)    │
└─────────────────────────────────────────────────────────┘
                          ▲
                          │
┌─────────────────────────────────────────────────────────┐
│                   Bridge Orchestrator                   │
│  - Device lifecycle management                          │
│  - Polling coordination                                 │
│  - State persistence                                    │
└─────────────────────────────────────────────────────────┘
                          ▲
                          │
┌─────────────────────────────────────────────────────────┐
│              Adaptive Polling Engine                    │
│  - Dynamic vs static register handling                  │
│  - Multi-register read optimization                     │
│  - Per-device poll scheduling                           │
└─────────────────────────────────────────────────────────┘
                          ▲
                          │
┌─────────────────────────────────────────────────────────┐
│                  Device Abstraction                     │
│  - Driver interface                                     │
│  - Register definitions                                 │
│  - Constraints & protection                             │
└─────────────────────────────────────────────────────────┘
                          ▲
                          │
┌─────────────────────────────────────────────────────────┐
│              Mutex Layer (RTU only)                     │
│  - async-mutex for serial bus protection                │
│  - Prevents simultaneous device access                  │
└─────────────────────────────────────────────────────────┘
                          ▲
                          │
┌─────────────────────────────────────────────────────────┐
│                  Transport Layer                        │
│  - RTU (serial) transport via modbus-serial             │
│  - TCP transport via modbus-serial                      │
│  - RTU-over-TCP bridges                                 │
└─────────────────────────────────────────────────────────┘

Transport Implementation: Wraps modbus-serial to provide:

  • Unified interface for RTU and TCP transports
  • Connection management and recovery
  • Error normalization and retry logic
  • Integration with mutex layer for RTU operations

Function Codes of the Transport Interface

The Transport interface (packages/driver-types/src/transport.ts) provides one method for each of these function codes:

Code Function Transport method
0x01 Read Coils readCoils
0x02 Read Discrete Inputs readDiscreteInputs
0x03 Read Holding Registers readHoldingRegisters
0x04 Read Input Registers readInputRegisters
0x05 Write Single Coil writeSingleCoil
0x06 Write Single Register writeSingleRegister
0x0F Write Multiple Coils writeMultipleCoils
0x10 Write Multiple Registers writeMultipleRegisters

Other function codes, such as file records (0x14, 0x15), are not part of the interface.

The emulator serves 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x0F and 0x10. See packages/emulator/README.md (Supported Function Codes).

Key Architectural Decisions

1. Mutex Strategy: Transport-Aware Locking

Problem: Modbus RTU requires sequential access (single bus), but Modbus TCP supports concurrent connections.

Solution: Transport-aware locking - mutex only applied to RTU/RTU-over-TCP operations, TCP operations execute directly without locking.

Implementation: packages/transport/src/manager.ts

Rationale: Maximizes throughput for TCP devices while ensuring RTU safety.

2. Adaptive Polling: Three Register Types

Problem: Some registers change frequently (voltage), others rarely (serial number).

Solution: Three polling strategies with different rates.

Poll Type Use Case Default Interval Behavior
dynamic Real-time measurements 1-10 seconds Continuous polling
static Device metadata Once at startup Read once, cache forever
on-demand Configuration registers Never Only when explicitly requested

Register configuration: Each register specifies address, type, format, poll type, and optional custom interval.

Implementation: packages/mqtt-bridge/src/polling/

Rationale: Reduces bus traffic by 60-80% compared to uniform polling.

3. Multi-Register Read Optimization

Problem: Reading registers individually wastes bus bandwidth.

Solution: Batch adjacent registers into single read operations.

Example: Reading registers [0, 1, 2, 5, 6, 7]

  • Without optimization: 6 read operations
  • With optimization: 2 read operations ([0-2], [5-7])

Algorithm:

  1. Sort registers by address
  2. Group consecutive registers with gaps ≤ threshold
  3. Ensure groups respect device batch size limits
  4. Only batch registers of same type (holding, input, etc.)

Configuration: Per-device settings for gap threshold (default: 10 registers) and max batch size (default: 80 registers, per Modbus spec).

Implementation: packages/mqtt-bridge/src/polling/

Rationale: Reduces read operations by 70-90% for typical devices.

4. Runtime Configuration via MQTT

Problem: Adding/modifying devices requires bridge restart.

Solution: MQTT-based configuration with state persistence.

MQTT Topic Structure:

modbus/
├── config/
│   ├── devices/
│   │   ├── add              # Add new device
│   │   ├── remove           # Remove device
│   │   └── {deviceId}/
│   │       ├── polling      # Update polling config
│   │       ├── enabled      # Enable/disable device
│   │       └── registers    # Update register definitions
│   └── bridge/
│       └── reload           # Reload configuration
│
├── {deviceId}/
│   ├── data                 # Device data publications
│   ├── set                  # Data points to write
│   │   └── result           # Result of each write message
│   ├── status/              # Device status
│   └── errors/              # Device errors
│
└── bridge/
    ├── status/              # Bridge status
    └── discovery/           # Discovery results

State Persistence:

  • File: ./data/bridge-state.json (configurable)
  • Format: JSON with semver schema versioning
  • Auto-save: On changes + periodic (5 min) + graceful shutdown
  • Recovery: Restore devices and polling state on startup

5. Device Discovery & Auto-Detection

Problem: Manual configuration of serial parameters is error-prone.

Solution: Multi-stage discovery process.

Discovery Stages:

  1. Serial parameter detection - Test combinations of baud rates (9600, 19200, 38400, 115200), parities (none, even, odd), and stop bits (1, 2)
  2. Device address scan - Probe slave IDs 1-247 for responses
  3. Device type identification - Match response patterns against known device signatures

Output: Discovery results include slave ID, serial parameters, identified device type, confidence score, manufacturer, and model.

Implementation: packages/device-profiler/src/

6. Error Handling & Publishing

Strategy: Publish all errors to MQTT for monitoring.

Error Categories:

Category Action MQTT Topic
Timeout Retry 3x modbus/{deviceId}/errors/timeout
CRC error Retry 3x modbus/{deviceId}/errors/crc
Invalid response Retry 3x modbus/{deviceId}/errors/invalid
Modbus exception Log & continue modbus/{deviceId}/errors/exception
Connection lost Reconnect modbus/{deviceId}/events/disconnected

Error Message Format: Published errors include timestamp, error type, operation details (read/write, address, count), retry attempt number, and human-readable message.

7. Device Constraints & Protection

Problem: Devices have different limits and forbidden register ranges.

Solution: Per-device constraint configuration.

Constraints include:

  • Max read/write sizes (Modbus standard: 125 read registers, 123 write registers, 2000 coils)
  • Device-specific forbidden register ranges (both read and write)
  • Range specifications include type, start/end addresses, and optional reason

Enforcement: Validate all operations before execution, reject requests that violate constraints.

Implementation: packages/driver-types/src/device-driver.ts

8. Connection Management & Recovery

Problem: Devices disconnect unpredictably (serial adapter removal, network issues).

Solution: Automatic reconnection with exponential backoff.

Algorithm:

  1. Start with 1 second delay
  2. Publish disconnection status to MQTT
  3. Attempt reconnection
  4. On failure, double delay (capped at 60 seconds)
  5. Repeat until successful or manually stopped

Reconnection Triggers:

  • Serial adapter disconnection (USB removal)
  • TCP connection timeout
  • Repeated communication failures (>10 errors)

9. Diagnostics & Issue Detection

Proactive Issue Detection:

  • High error rate (>5% of operations failing)
  • Slow responses (>500ms average latency)
  • Connection flapping (>10 reconnects per hour)
  • Wrong configuration (consistent CRC errors indicating wrong baud rate/parity)
  • Bus contention (should never occur with proper mutex usage)

Status Publishing: Device status includes timestamp, connection state, poll rate, average latency, error rate, and detected issues with severity levels (warning, error, critical).

10. Data Transformation & External API

Problem: Device-specific encodings (integers with multipliers, decimal date formats, BCD) should not leak to external consumers.

Solution: Two-layer data representation with device drivers owning the transformation.

Architecture Layers:

  1. Internal Layer (device-specific, opaque to consumers):

    • Raw Modbus register definitions with wire formats (int16, uint16, float32, etc.)
    • Device-specific transformations (multipliers, offsets, custom decoders)
    • Register address mappings and batch optimization
  2. External Layer (standardized API):

    • Semantic data points identified by meaningful IDs ("voltage_l1", "total_energy")
    • Standard data types and units (canonical definitions in packages/driver-types/src/)
    • Polling configuration by data point, not by register

Transformation Examples:

Device Encoding Raw Value External Value
uint16 × 0.1 (voltage) 2305 230.5 (float)
Decimal date (YYMMDD) 251220 "2025-12-20"
Decimal time (HHMMSS) 103045 "10:30:45"
BCD-encoded 0x1234 1234 (integer)

Responsibilities:

  • Device Drivers: Define data point catalog, implement transformations, optimize register reads
  • Consumers: Configure polling by semantic data point IDs, receive standardized values
  • Bridge Core: Provide transformation helpers, define canonical types/units, coordinate polling

Extensibility:

  • Data types: packages/driver-types/src/data-types.ts
  • Units: packages/driver-types/src/units.ts
  • Standard transforms: packages/driver-sdk/src/

Rationale:

  • Consumers configure "what" (voltage, energy) not "how" (register addresses and formats)
  • Device complexity is encapsulated and transparent to users
  • New data types/units extend the system without modifying existing devices
  • Clear separation enables independent device driver development

Data Flow

1. Device Registration (Runtime)

User → MQTT Publish → modbus/config/devices/add
              ↓
    Bridge receives configuration
              ↓
    Validate configuration (Zod schema)
              ↓
    Instantiate device driver
              ↓
    Add to polling scheduler
              ↓
    Persist to state file
              ↓
    Publish confirmation

2. Polling Cycle

Scheduler triggers poll (interval-based)
              ↓
    Mutex acquire (if RTU)
              ↓
    Optimize register reads (batching)
              ↓
    Execute Modbus read operations
              ↓
    Mutex release (if RTU)
              ↓
    Parse & format data
              ↓
    Publish to MQTT (modbus/{deviceId}/data)
              ↓
    Update statistics & diagnostics

3. Error Handling Flow

Modbus operation fails
              ↓
    Classify error type
              ↓
    Retry logic (3 attempts with backoff)
              ↓
    Publish error to MQTT
              ↓
    Update error statistics
              ↓
    Trigger diagnostics check
              ↓
    If critical: Initiate reconnection

Scaling Considerations

Performance Targets

Metric Target Notes
Devices per bridge 50+ RTU limited by bus speed
Poll rate (RTU) 10-50 Hz Depends on baud rate & registers
Poll rate (TCP) 100+ Hz Per device, concurrent
Mutex wait time <10ms Average wait for RTU devices
Memory per device <1MB Including polling state
State file size <100KB For 50 devices

RTU Bus Limitations

Serial Bus Math:

Baud rate: 9600 bps
Frame size: ~12 bytes (typical Modbus RTU frame)
Frame time: ~10ms at 9600 baud

For 10 devices @ 9600 baud:
  10 devices × 10ms/frame = 100ms/cycle
  Max poll rate: ~10 Hz across all devices

Optimization Strategies:

  1. Use higher baud rates (38400, 115200) if supported
  2. Batch register reads to reduce frame count
  3. Prioritize dynamic registers (static polled once)

TCP Scalability

Concurrent TCP Devices:

  • No mutex required
  • Limited only by network bandwidth and CPU
  • Recommended: Max 100 devices per bridge instance

Horizontal Scaling:

  • Run multiple bridge instances for >100 devices
  • Partition by device groups or buildings
  • Use MQTT prefix to avoid topic collisions

Testing Strategy

Test Pyramid

         ╱╲
        ╱  ╲  E2E Tests (Emulator + MQTT)
       ╱────╲
      ╱      ╲  Integration Tests (Device drivers)
     ╱────────╲
    ╱          ╲  Unit Tests (Polling, mutex, parsing)
   ╱────────────╲

Emulator Usage

Purpose: Test device drivers without physical hardware.

Capabilities:

  • Emulate Modbus devices over RTU, TCP or an in-memory transport
  • Configurable holding register, input register, coil and discrete input values
  • Function codes 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x0F and 0x10 (see packages/emulator/README.md, Supported Function Codes)
  • Simulated response timing (command detection, processing and per-register delays)

Usage: See packages/emulator/src/ for usage examples and tests.

Security Considerations

MQTT Security

  • Authentication: Support username/password, TLS client certificates
  • Authorization: Use MQTT ACLs to restrict topic access
  • Encryption: TLS 1.2+ for MQTT connections

Modbus Security

  • Input Validation: Validate all register addresses, counts, values
  • Forbidden Ranges: Prevent writes to protected registers
  • Rate Limiting: Prevent DoS via excessive write operations

State File Security

  • Permissions: chmod 600 for state file (owner read/write only)
  • Validation: Validate schema version before loading
  • Migration: Safe migration between schema versions

Deployment Patterns

Systemd Service

Service configuration: Simple service type, automatic restart, runs as dedicated user, configurable state file location.

Configuration: See packages/mqtt-bridge/systemd/ directory for the service unit file and installation guide.

Monitoring & Observability

MQTT Status Topics

modbus/bridge/status/health     # Overall bridge health
modbus/{deviceId}/status/*      # Per-device status
modbus/{deviceId}/errors/*      # Per-device errors

Integration with Monitoring Systems

Telegraf: MQTT consumer input plugin subscribes to data and status topics, parses JSON format.

Prometheus (via converter):

  • Export metrics in Prometheus format
  • Scrape via HTTP endpoint
  • Standard Modbus metrics (voltage, current, power)

Grafana Dashboards:

  • Device overview (status, poll rates, errors)
  • Performance metrics (latency, throughput)
  • Error trends and diagnostics

Plugin Architecture for Third-Party Drivers

Overview

Device drivers can be distributed as independent npm packages, enabling:

  • Community-contributed drivers without modifying core codebase
  • Private/proprietary device drivers
  • Rapid driver development with standardized tooling
  • Ecosystem growth independent of core releases

Package Structure

@ya-modbus/driver-types      # TypeScript type definitions (types-only)
@ya-modbus/driver-sdk        # Runtime SDK (base classes, helpers, transforms)
@ya-modbus/driver-loader     # Dynamic driver loading
@ya-modbus/device-profiler   # Development tools (register scanning, device discovery)
@ya-modbus/cli               # CLI tool (production + dev features)
@ya-modbus/mqtt-bridge       # Core bridge (loads drivers dynamically)

Dependency flow:

  • driver-types: No dependencies (pure types)
  • driver-sdk: Depends on driver-types
  • driver-loader: Depends on driver-types
  • device-profiler: Depends on driver-loader, driver-types, transport
  • emulator: Depends on driver-loader
  • cli: Depends on driver-loader, driver-types, transport
  • mqtt-bridge: Depends on driver-loader, driver-types, transport
  • Third-party drivers: Depend on driver-sdk, driver-types

No cyclic dependencies: SDK is contract, mqtt-bridge is runtime, drivers are plugins.

Driver Discovery

Convention-based loading:

  1. Package naming:
    • Drivers in this repository: @ya-modbus/driver-<name> (e.g., @ya-modbus/driver-xymd1)
    • Third-party drivers, recommended: ya-modbus-driver-<name> (e.g., ya-modbus-driver-solar)
    • Third-party scoped packages: @<scope>/ya-modbus-driver-<name> (e.g., @acme/ya-modbus-driver-solar)
    • <name> and <scope> use only lowercase letters, numbers and hyphens. The MQTT bridge rejects every other driver name; the rule lives in packages/driver-loader/src/driver-package-name.ts
    • Required: keyword "ya-modbus-driver" in package.json
  2. Standard exports: createDriver factory, optional DEFAULT_CONFIG, SUPPORTED_CONFIG, DEVICES

Example third-party driver (ya-modbus-driver-solar):

{
  "name": "ya-modbus-driver-solar",
  "description": "Drivers for Acme Solar inverters (X1000, X2000, X5000 series)",
  "keywords": ["ya-modbus-driver", "modbus", "solar"],
  "main": "dist/index.js",
  "types": "dist/index.d.ts",
  "peerDependencies": {
    "@ya-modbus/driver-sdk": "^1.0.0"
  }
}

Single package, multiple device types: Package exports single createDriver factory function that handles all device variants.

Auto-detection: Driver can auto-detect device type from identification registers when device config omitted.

Runtime loading: Core bridge imports package and calls createDriver(config) with optional device parameter.

Driver Interface Contract

Stable public API (@ya-modbus/driver-sdk):

  • Driver factory function pattern (functional approach preferred)
  • Data point definitions (semantic IDs, types, units)
  • Standard transformation helpers (multipliers, BCD, decimal dates, etc.)
  • Constraint types (forbidden ranges, batch limits, timing)

Implementation: See packages/driver-*/src/ for reference driver implementations (e.g., driver-ex9em, driver-xymd1).

Key principle: Drivers transform device-specific encodings to standard data types transparently.

Development Tooling

CLI commands for driver developers:

Production use (global install):

npm install -g @ya-modbus/cli ya-modbus-driver-solar
ya-modbus read --driver ya-modbus-driver-solar --port /dev/ttyUSB0 \
  --slave-id 1 --data-point voltage_l1

Development use (local devDependencies):

# In driver package directory
npx ya-modbus read --port /dev/ttyUSB0 --slave-id 1 --data-point voltage_l1
npx ya-modbus scan-registers --port /dev/ttyUSB0 --slave-id 1
npx ya-modbus characterize --port /dev/ttyUSB0 --slave-id 1 --output profile.json

Development commands (require @ya-modbus/device-profiler):

  • discover - Auto-detect connection parameters (baud, parity, slave ID)
  • scan-registers - Find readable/writable register ranges
  • test-limits - Determine max batch size, min timing delays
  • characterize - Complete device profiling (all discovery + limits)

Production commands (always available):

  • read - Read data points
  • write - Write data points
  • provision - Initial device configuration

Test Harness

Emulator-based testing for driver development.

Test harness provides:

  • Mock transport (stubs Modbus communication)
  • Emulator integration (software Modbus devices)
  • Assertion helpers (data point validation)
  • Fast test cycles (no hardware required)

Usage examples: See packages/driver-*/src/**/*.test.ts for test patterns (e.g., driver-ex9em, driver-xymd1).

Versioning & Compatibility

Semantic versioning for SDK and drivers independently:

SDK versioning: Follows semantic versioning (major.minor.patch).

Driver compatibility: Declared via peerDependencies in driver's package.json.

Runtime validation: Core bridge validates driver SDK compatibility at load time.

Deprecation policy: 6-12 month warning before removing SDK features.

Reference: See docs/DRIVER-DEVELOPMENT.md for version management details.

Device Characterization

Automated device discovery helps driver developers:

  1. Connection parameters: Auto-detect baud rate, parity, stop bits, slave ID
  2. Register ranges: Scan for readable/writable registers, find forbidden areas
  3. Operation limits: Test max batch size, minimum inter-command delays
  4. Access restrictions: Identify read-protected, write-protected registers
  5. Authentication: Detect unlock sequences (password registers)
  6. Quirks: Find timing requirements, order dependencies

Output: JSON profile with connection parameters, operation limits, forbidden ranges, access restrictions, and device quirks.

Purpose: Bootstraps driver development and validates device documentation.

Schema: See packages/device-profiler/src/ for device profiling types and structure.

Built-in Drivers as Plugins

No special casing: Built-in drivers (e.g., @ya-modbus/driver-ex9em, @ya-modbus/driver-xymd1) use same interface as third-party drivers.

Benefits:

  • Consistent architecture (no dual implementation paths)
  • Built-in drivers serve as reference implementations
  • Users install only needed drivers (smaller footprint)
  • Clear separation between core bridge and device-specific code

Package Installation

Manual installation via package manager (not automated):

# User installs bridge + needed drivers
npm install -g ya-modbus ya-modbus-driver-solar

# Or via package.json for project
npm install ya-modbus ya-modbus-driver-solar

Rationale:

  • Security (no arbitrary code execution via config)
  • Explicit dependencies (package-lock.json tracks versions)
  • Standard npm workflow (familiar to users)

Configuration

Device config references driver by package name:

{
  "driver": "ya-modbus-driver-solar",
  "device": "X1000" // Optional - auto-detect if omitted
}

Configuration pattern:

  • driver: Package name in one of the forms above (e.g., ya-modbus-driver-solar or @acme/ya-modbus-driver-solar)
  • device: Optional device variant within package (use ya-modbus list-devices to see options)
  • Auto-detection: Omit device and driver reads identification registers

Benefits:

  • Simple configuration (package name only, no class names)
  • Auto-detection reduces configuration burden
  • Single package handles entire device family

Version management: Handled by package manager (package.json, not device config).

Examples: See examples/config/ for configuration patterns.

Ecosystem Benefits

For driver developers:

  • Standardized SDK reduces learning curve
  • Test harness accelerates development
  • Characterization tools automate discovery
  • Independent release cycle
  • Reusable across projects

For users:

  • Large driver ecosystem (community + commercial)
  • Install only needed drivers (smaller footprint)
  • Mix built-in and third-party drivers
  • Private drivers possible (no public disclosure)

For core project:

  • Focus on bridge functionality, not device coverage
  • Community contributions without core PRs
  • Faster iteration (drivers evolve independently)
  • Clear interface boundaries

Migration Path

The plugin architecture is fully implemented:

  1. Types extracted to @ya-modbus/driver-types
  2. Runtime SDK in @ya-modbus/driver-sdk
  3. Device profiling tools in @ya-modbus/device-profiler
  4. Built-in drivers use SDK (e.g., @ya-modbus/driver-ex9em, @ya-modbus/driver-xymd1)
  5. @ya-modbus/mqtt-bridge loads drivers via @ya-modbus/driver-loader

Drivers follow the same interface pattern (same device IDs, behavior).

Future Enhancements

Phase 2 Considerations

  1. Web UI: Configuration management, device status dashboard
  2. Advanced Discovery: Device fingerprinting, auto-driver selection
  3. Historical Data: Optional built-in time-series storage
  4. Redundancy: High-availability with failover
  5. Cloud Integration: AWS IoT Core, Azure IoT Hub connectors

Extensibility Points

  • Custom Transports: BACnet, KNX, other protocols
  • Custom Converters: User-defined data transformations
  • Plugin System: Third-party device drivers (see Plugin Architecture above)
  • Scripting: Lua/JavaScript for custom logic